Blue Lens Strobe Multi-Zone Refrigerant Monitor – Refrigerants: 0 to 10,000 ppm, Ammonia: 25 to 10,000 ppm Carbon Dioxide: 300 to 8,000 ppm, ±1 ppm ±10% from 0-1000 ppm (refrigerants); ±10 ppm ±10% from 0-10

SKU 010-LKC928 Category Brand:

$497.70 / Each

Available on backorder

Available on backorder

Description

  • Proprietary infrared (NDIR) sensor accurately detects the presence of a target gas down to an industry-leading 1 ppm Minimum Detection Level (MDL)
  • Sensor is not prone to false alarms caused by cross-interference from other gases or sudden changes in temperature or humidity
  • Gas library contains 60+ refrigerants, including CFCs, HFCs, HCFCs, HFOs and natural refrigerants (R-744, R-717)
  • Backlit display shows real-time concentration readings and makes configuration and self-diagnostics intuitive
  • Capable of monitoring up-to 16 zones (expandable up to 48 sample points) and detecting multiple gases with a single monitor
  • Two optional analog outputs (4-20mA) and Modbus communications (slave) for integration with third-party BMS / BAS control systems
  • Three user-configurable relays (leak, spill and evacuate) may be used to activate external beacons / sounders, ventilation or other countermeasures

Additional information

Weight 0.5443104 kg
Dimensions 15.24 × 15.24 × 7.62 cm
Manufacturer Model

3015-8044

Measuring Range

Refrigerants: 0 to 10,000 ppm, Ammonia: 25 to 10,000 ppm Carbon Dioxide: 300 to 8,000 ppm

Accuracy

±1 ppm ±10% from 0-1000 ppm (refrigerants); ±10 ppm ±10% from 0-10,000 ppm (Ammonia); ±5 PPM ±5% from 300-1000 ppm (CO2)

Resolution

1 ppm

Sampling Distance

0 to 1,200' (0 to 365 m)